Capacity factor: why is 1 MW not always 1 MW?
Run three 100 MW plants for a year and count what they make
- Foundations · L1
- Lesson 5 of 14
- 15 min
- After lesson 1
- Completed
The idea in one table: three plants of 100 MW, one year (2025 U.S. capacity factors)
| Plant, 100 MW | Energy in the year | Capacity factor |
|---|---|---|
| Nuclear | 798,000 MWh | 91.1% |
| Wind | 296,088 MWh | 33.8% |
| Solar | 210,240 MWh | 24.0% |
| At full size every hour | 876,000 MWh | 100% |
Count one day: the 100 MW solar farm on 3 September 2025
The day hour by hour, MW
| Hour from | MW | Hour from | MW |
|---|---|---|---|
| 00:00 | 0 | 12:00 | 76 |
| 01:00 | 0 | 13:00 | 72 |
| 02:00 | 0 | 14:00 | 53 |
| 03:00 | 0 | 15:00 | 72 |
| 04:00 | 0 | 16:00 | 79 |
| 05:00 | 0 | 17:00 | 63 |
| 06:00 | 0 | 18:00 | 31 |
| 07:00 | 3 | 19:00 | 6 |
| 08:00 | 32 | 20:00 | 0 |
| 09:00 | 56 | 21:00 | 0 |
| 10:00 | 62 | 22:00 | 0 |
| 11:00 | 71 | 23:00 | 0 |
Energy made: the 24 outputs add up to 676 MWh. Capacity factor: 676 ÷ (100 × 24) = 28.2%. The night hours count too.
The power curve of an illustrative 3 MW wind turbine
- Below 3 m/s (cut-in): no electricity.
- 3 to 12 m/s (rated): output follows the cube of the wind speed; doubling a speed within this range gives eight times the output.
- 12 to 25 m/s (cut-out): output holds at 3,000 kW.
- Above 25 m/s: the turbine shuts down to protect itself.
With JavaScript on, you work through this step by step: a year of output, the solar day, the turbine's power curve and a quick calculation.
Real data. Capacity factors are the 2025 U.S. averages from EIA's Electric Power Monthly, Table 6.07.B (released 23 October 2026).
Real shapes, reshaped. Wind and solar keep the Southwest Power Pool's 2025 hour-by-hour pattern (EIA-930), reshaped month by month to those U.S. averages. So the solar day is illustrative, not one farm's meter.
Illustrative. The nuclear plant's refuelling outage and the 3 MW wind turbine.
Need a refresher? Toolbox K1 (MW held for 8,760 h is MWh) and K2 (capacity factor as a rate).
What you just did, as diagrams
- Capacity factor
- Energy made ÷ (size × hours): the share of the most a plant could make that it actually made.
- Same MW, different MWh
- In 2025, U.S. nuclear plants ran at 91.1% of their size on average, wind at 33.8% and solar at 24.0%.
- Every hour counts
- Nights and calm hours stay in the count, which is why solar's capacity factor is low.
- The cube law
- Between cut-in (3 m/s) and rated speed (12 m/s), twice the wind speed gives this turbine eight times the output.
- Rated and cut-out speeds
- From the rated speed to cut-out (25 m/s) the output holds at 3,000 kW; above cut-out the turbine shuts down.
Go deeper · AnalystCapacity factor depends on the period and the place
Every fleet’s capacity factor changes from month to month. U.S. averages in 2025 (EIA, Table 6.07.B):
| Fleet | Lowest month | Highest month |
|---|---|---|
| Wind | 23.1% (September) | 43.1% (March) |
| Solar | 13.1% (December) | 31.9% (June and July) |
| Nuclear | 81.0% (October) | 99.2% (December) |
Nuclear dips in spring and fall, the seasons when many reactors stop to refuel.
- Availability is not capacity factor. A solar farm can be ready all night and still make nothing.
- Curtailment lowers it. A wind farm turned down by the grid makes less than its weather allowed (lesson 0).
- Sites differ. The U.S. averages hide windy plains and sunny deserts; Prairie Town’s shapes come from one region.
Lesson 7 uses capacity factor to spread a plant’s building cost over the MWh it makes.
Go deeper · ModelerThe power curve, from physics to measurements
Power in the wind. Through a rotor, the wind carries \(P_\text{wind} = \tfrac{1}{2}\rho A v^3\).
| Symbol | Meaning | The lesson’s turbine |
|---|---|---|
| \(\rho\) | air density, kg/m³ | 1.225 kg/m³, sea level |
| \(A\) | area the blades sweep, m² | 7,854 m², a 100 m rotor |
| \(v\) | wind speed, m/s | 12 m/s, its rated speed |
| \(P_\text{wind}\) | power in the wind, kW | 8,313 kW |
What the turbine captures. It makes 3,000 kW at 12 m/s, so its power coefficient is \(C_p = 3{,}000 / 8{,}313 = 0.36\). No rotor can capture more than \(16/27 \approx 0.593\) of the wind’s power: the Betz limit.
The lesson’s clean power curve, output \(P\) in kW at wind speed \(v\) in m/s:
\[ P(v) = \begin{cases} 3000 \times (v/12)^3 \text{ kW} & 3 \le v < 12 \text{ m/s}\\ 3000 \text{ kW} & 12 \le v \le 25 \text{ m/s}\\ 0 & \text{otherwise.} \end{cases} \]
A measured curve. Real 10-minute averages scatter around a curve: gusts, air density and the turbine’s own controls move each one.
The chart shows a 1.5 MW research turbine that NREL tested in 2011, beside a clean curve built the same way for it: the cube law at its best \(C_p\), 0.52, capped at 1,500 kW.
| Wind speed, m/s | Measured average, kW | Spread (±1 SD), kW | Clean curve, kW |
|---|---|---|---|
| 3.97 | 59 | 28 | 93 |
| 5.99 | 304 | 52 | 319 |
| 8.00 | 742 | 74 | 759 |
| 10.03 | 1,200 | 75 | 1,497 |
| 11.98 | 1,400 | 127 | 1,500 |
| 13.97 | 1,482 | 47 | 1,500 |
| 15.98 | 1,497 | 17 | 1,500 |
From about 6 to 8 m/s the averages follow the cube law closely. Above that they bend over gradually: full power comes near 14 m/s, not at a sharp corner near 10 m/s.
Source: NREL, Power Performance Test Report for the U.S. Department of Energy 1.5-Megawatt Wind Turbine, Table 6 (2015; test from February to June 2011).
- Research. Estimating a wind farm’s curve, with honest error bars, from few records is an active research topic (Li et al., 2023; open code: mfgpr-wind-power-curve).
- Next. Modeler lesson M9 fits a curve to data; bridge B2 computes capacity factors in Python.
Go deeperWhat this lesson leaves out
- The wind and solar shapes are whole regional fleets, smoother than any single farm.
- Wind and solar are reshaped so that each month matches the U.S. average and the best hours reach full size.
- The seasons are national; the hours are those of one region.
- The nuclear plant's outage and the turbine are illustrative, not a real plant or model.
- Air density changes with temperature and altitude, which shifts a real power curve.
- The clean curve has no spread: a real turbine's output scatters around it (the measured curve above).
Check yourself
Myth or fact? “A 100 MW wind farm makes 100 MW most of the time.”
- Myth
- Fact
Answer
Myth. In 2025, U.S. wind farms made 33.8% of what they would have made at full size, and the cube law makes their output swing with every change in the wind.
Myth or fact? “A solar farm with a 24.0% capacity factor is broken three-quarters of the time.”
- Myth
- Fact
Answer
Myth. At night and under clouds it works as designed: the sun, not the machine, sets most of the gap.
Myth or fact? “Doubling the wind speed doubles a turbine's output.”
- Myth
- Fact
Answer
Myth. On this lesson's turbine it gives eight times the output (2 × 2 × 2), but only while both speeds lie between cut-in (3 m/s) and rated (12 m/s); then output holds at rated power until cut-out (25 m/s).
A 50 MW solar farm made 105,120 MWh in a year of 8,760 hours. What was its capacity factor?
- 24.0%
- 48.0%
- 12.0%
- 100%
Answer
24.0%: 105,120 ÷ (50 × 8,760) = 0.240. Leaving out the night hours would wrongly raise it: capacity factor counts every hour. Using 100 MW would halve it.
At the 2025 U.S. average of 91.1%, how much energy does 1 MW of nuclear make in a year?
- 8,760 MWh
- 7,980 MWh
- 911 MWh
- 91.1 MWh
Answer
7,980 MWh: 1 MW × 8,760 h × 0.911. The full 8,760 MWh would need every hour at full size.
Numbers, sources and what’s next
Numbers to remember
| Number | What it means | Source |
|---|---|---|
| 91.1% | Average capacity factor of U.S. nuclear plants in 2025. | EIA, Electric Power Monthly, Table 6.07.B · 2025 data (final), released October 2026 |
| 33.8% | Average capacity factor of U.S. wind farms in 2025. | EIA, Electric Power Monthly, Table 6.07.B · 2025 data (final), released October 2026 |
| 24.0% | Average capacity factor of U.S. utility-scale solar photovoltaic farms in 2025. | EIA, Electric Power Monthly, Table 6.07.B · 2025 data (final), released October 2026 |
| 18–24 months | How often U.S. reactors typically refuel, mostly in spring and fall. | EIA, Today in Energy · as of October 2022 |
| 10,791 kWh | Electricity bought in a year by an average U.S. residential customer (a yearly total, not an hourly need). | EIA, Frequently Asked Questions · data for 2022 |
Next on the starter path
In the real world
EIA publishes these capacity factors every month for every kind of plant. Turning a wind farm's scattered measurements into a power curve with honest error bars is still a research question (Li et al., 2023).
Case file CF8: learning a wind turbine's power curve from scarce data.
Sources and further reading
- EIA. Electric Power Monthly, Table 6.07.B: Capacity factors for utility scale generators primarily using non-fossil fuels. Data for August 2026, released 23 October 2026.
- EIA. Hourly Electric Grid Monitor (Form EIA-930): the Southwest Power Pool's 2025 wind and solar shapes.
- EIA (2022). Daily U.S. summer nuclear capacity outages were 19% lower this summer than last summer. Today in Energy.
- NREL (2015). Power Performance Test Report for the U.S. Department of Energy 1.5-Megawatt Wind Turbine. Technical Report NREL/TP-5000-63684 (test February to June 2011).
- Li, H., et al. (2023). A Multi-Fidelity Gaussian Process Regression Method for Probabilistic Wind Farm Power Curve Estimation. ASME IDETC/CIE 2023.
Spotted an error, or stuck? Write to hlli@ksu.edu. Corrections are made in place and dated here.
Text licensed CC BY 4.0, code MIT: teachers and students may reuse and adapt it, with credit to Honglin Li.