Rates and efficiencies
Chain per-unit numbers, turn a heat rate into an efficiency, and follow the losses
- Math toolbox
- 10 min guided · about 10 min practice
- After K1
- Completed
Rates and efficiencies, in five moves
- A rate is one amount per another: 10,791 kWh bought in a year ÷ 8,760 h = 1.232 kW, an average of 1,232 W bought from the grid.
- Rates chain when the units cancel: 6.226 MMBtu per MWh × $3.85 per MMBtu = $23.97 per MWh, and × 52.91 kg CO₂ per MMBtu = 329 kg per MWh.
- Efficiency = 3.412 MMBtu per MWh ÷ heat rate: 54.8% for the combined-cycle plant, 37.3% for the peaker (heat rate 9.142).
- Losses multiply, and dividing undoes them: an 85% battery gives back 85 of 100 MWh; 100 MWh back needs 100 ÷ 0.85 = 117.6 MWh in, not 115.
- A capacity factor is energy made ÷ the most possible over the same period; for a year, 150 MW × 8,760 h × 33.8% = 444,132 MWh.
| Rate | Unit | Worked on this page |
|---|---|---|
| Average power bought from the grid | kW = kWh per hour | 10,791 kWh ÷ 8,760 h = 1.232 kW |
| Heat rate | MMBtu per MWh | 6.226 (combined-cycle), 9.142 (peaker) |
| Fuel cost | $ per MWh | 6.226 × $3.85 = $23.97 |
| CO₂ at the plant | kg per MWh | 6.226 × 52.91 = 329 kg |
| Efficiency | % (out ÷ in) | 3.412 ÷ 6.226 = 54.8% |
| Round trip | % (back ÷ in) | 117.6 MWh in, 100 MWh back at 85% |
| Capacity factor | % (made ÷ most possible) | 150 MW × 8,760 h × 33.8% = 444,132 MWh |
With JavaScript on, you work these out yourself, step by step.
- A home's 10,791 kWh a year: EIA, 2022 data, as in lesson 1.
- Heat rates 6.226 and 9.142 MMBtu per MWh: EIA, AEO2026 assumptions, Table 3 (April 2026). Gas $3.85 per MMBtu: EIA, 2025 average. Both as in lesson 7.
- 52.91 kg CO₂ per MMBtu of gas: EIA (checked 2 November 2026), as lessons 12 and 13 use it.
- CO₂ boundary: gas burned at the plant only. Producing and delivering the gas, and building the plant, are outside it.
- Lesson 0's town uses a rounded, illustrative 0.37 t (metric tonnes) of CO₂ per MWh instead.
- 3,412 Btu per kWh, so 3.412 MMBtu per MWh: EIA FAQ on plant efficiency (checked 3 November 2026).
- 85% round trip: lesson 13's battery, from NREL's 2025 battery cost study (June 2025); lesson 9's illustrative battery uses 80%.
- Prairie Town's 150 MW wind farm is illustrative; 33.8% is U.S. wind in 2025: EIA, Table 6.07.B (released 23 October 2026).
What you just did, as diagrams
- Rate
- One amount per another, such as $ per MWh; its unit says what was divided by what.
- Chaining rates
- Multiply rates when a unit cancels: MMBtu per MWh × $ per MMBtu gives $ per MWh.
- Heat rate and efficiency
- Efficiency = 3.412 ÷ heat rate in MMBtu per MWh: a higher heat rate means a lower efficiency.
- Losses in a chain
- Stage efficiencies multiply: 54.8% × 85% = 46.6%. To go backwards, divide.
- Capacity factor
- Energy made ÷ the most possible in the same hours: a ratio with no unit.
Go deeper · AnalystEIA's own units, and percent against percentage points
- Btu per kWh. EIA quotes heat rates in Btu per kWh. 6,226 Btu per kWh is the same rate as 6.226 MMBtu per MWh: a million Btu per thousand kWh.
- Efficiency in those units. \(\eta = 3{,}412 \div 6{,}226 = 54.8\%\), exactly as on this page.
- Points. From the peaker’s 37.3% to the combined-cycle plant’s 54.8% is 17.5 percentage points.
- Percent. Per MWh, the peaker burns \(9.142 \div 6.226 = 1.47\) times the gas: 47% more. Say which one you mean.
- Ratios hide a period. A capacity factor needs its hours: lesson 5 uses 8,760 for a year.
Go deeper · ModelerRates as fixed numbers in a model (a preview)
- A simplified example. One gas plant and one battery, in one-hour steps, so every flow is in MWh per hour.
- Decision. The model chooses \(g\), the MWh the gas plant makes in an hour: a decision variable.
- Goal. The least total cost. Each MWh costs its fuel, 6.226 × $3.85 = $23.97, plus variable O&M (VOM: variable operation and maintenance, in $ per MWh).
- Rules. The CO₂, 0.329 t per MWh made, adds up under a yearly cap; the battery gives back 85% of each MWh charged.
- One line. \(\text{cost in the hour} = (\mathrm{HR} \times p + \mathrm{VOM}) \times g\), with HR the heat rate (MMBtu per MWh) and \(p\) the gas price ($ per MMBtu).
- Why fixed rates. Each term is then a fixed number times a decision, so the model stays a linear program. A real plant’s heat rate changes with its output; a fixed one is a modelling choice.
- Where next. Lesson 13 writes the full model: two gas plants, CO₂ in tonnes, each modelled hour weighted by the hours it stands for. M3 builds one in a notebook.
Check yourself
Myth or fact? “A plant with a higher heat rate is more efficient.”
- Myth
- Fact
Answer
Myth. Heat rate is gas burned per MWh, so higher means more gas: 9.142 gives 37.3%, 6.226 gives 54.8%.
Myth or fact? “To get 100 MWh out of an 85% battery, charge 115 MWh.”
- Myth
- Fact
Answer
Myth. 115 × 0.85 = 97.75 MWh. Divide instead: 100 ÷ 0.85 = 117.6 MWh.
The peaker burns 9.142 MMBtu of gas per MWh, and gas costs $3.85 per MMBtu. Its fuel cost per MWh?
- $2.37
- $35.20
- $12.99
- $0.42
Answer
$35.20: 9.142 × 3.85, and MMBtu cancels. $2.37 divides instead; $12.99 adds numbers with different units.
A 100 MW plant made 438,000 MWh in a year of 8,760 hours. Its capacity factor?
- 1,200%
- 5%
- 50%
- 0.5%
Answer
50%: 438,000 ÷ (100 × 8,760) = 438,000 ÷ 876,000. Dividing by 365 days instead of 8,760 hours gives 1,200%, which no plant can reach.
Numbers, sources and what’s next
Numbers to remember
| Number | What it means | Source |
|---|---|---|
| 3.412 | MMBtu of energy in one MWh of electricity (3,412 Btu per kWh): efficiency = 3.412 ÷ heat rate. | EIA FAQ · checked 3 November 2026 |
| 6.226 · 9.142 | Heat rates in MMBtu per MWh of a new combined-cycle plant and a new peaker: 54.8% and 37.3% efficient. | EIA, AEO2026 assumptions, Table 3 (PDF) · April 2026 |
| 52.91 kg | CO₂ per MMBtu of natural gas burned. | EIA · checked 2 November 2026 |
| 85% | Round trip of lesson 13's lithium-ion battery: 85 MWh back for 100 MWh in. | NREL, 2025 battery cost study (PDF) · June 2025 |
| 8,760 h | Hours in a year of 365 days: the denominator of a yearly capacity factor or average. | 365 × 24 |
Next
Sources and further reading
- EIA. What is the efficiency of different types of power plants? (FAQ): 3,412 Btu per kWh divided by the heat rate.
- EIA (2026). Assumptions to the Annual Energy Outlook 2026: Electricity Market Module (PDF). Table 3: heat rates.
- EIA. Carbon Dioxide Emissions Coefficients; Electric Power Annual, Table 7.4 (cost of gas to power plants); Electric Power Monthly, Table 6.07.B (capacity factors); How much electricity does an American home use? (FAQ).
- Cole, Ramasamy and Turan (2025). Cost Projections for Utility-Scale Battery Storage: 2025 Update (NREL, PDF): round-trip efficiency.
- Where this is used: lesson 1 (average power), lesson 5 (capacity factor), lesson 7 (fuel cost per MWh), lesson 9 and lesson 13 (round trip). Toolbox K1 covers the units underneath; K3 turns building costs into yearly costs.
Spotted an error, or stuck? Write to hlli@ksu.edu. Corrections are made in place and dated here.
Text licensed CC BY 4.0, code MIT: teachers and students may reuse and adapt it, with credit to Honglin Li.